Conditions of Use: |
Land Use |
---|---|
Usage: | Common Units |
Output Type: | AC Three Phase |
Cooling Method: |
Water Cooling |
Installation Method: |
Fixed |
Generator Type: |
Diesel Generator |
Customization: |
---|
Suppliers with verified business licenses
Product name
|
R250
|
|||
Power output voltage(DC)
|
Max. 100 Vdc at 120 Vac input
|
|||
Continual current
|
16A
|
|||
Max transient currrent
|
10ADC,≤10s
|
|||
Power intput voltage(AC)
|
120(90-140)Vac,1 phase 2 wire jumper selectable
|
|||
Power
|
Max 1000VA (240 Vac)
|
|||
Net Weight
|
0.32 kg
|
AVR R250
|
|||||
Voltage regulation
|
Around ± 0.5 %
|
||||
Supply range
|
85 to 139 V
|
||||
Potentiometer for voltage setting
|
1000Ω /0.5W min. setting range ±5%
|
||||
Operating at 50 Hz
|
Threshold at 48 Hz without LAM forimpactsbetween 30 and 40% of the rated
Load
|
||||
Threshold at 48 Hz with LAM 13% forimpacts between 40 and 70% of the rated
Load.
|
|||||
Threshold at 48 Hz with LAM 25% for impacts > 70% of the rated load
|
|||||
Operating at 60 Hz
|
Threshold at 58 Hz without LAM forimpacts between 30 and 40% of the
Rated load
|
||||
Threshold at 58Hz with LAM 13% for impacts 40 and 70% of the rated load
|
|||||
Threshold at 58Hz with LAM 25% for impacts > 70% of the rated load
|
|||||
Specific operating
|
Threshold at 57Hz without LAM for speed variations at a steady state > 2 Hz
|
||||
Threshold at 65Hz without LAM for speed and tractelec / gearlec (U/F gradient)
|
|||||
Special: the factory setting 48Hz 2U/F gradient; a special programme is
Possible on request.
|
|||||
Threshold at 47.5 Hz without LAM for speed variations at a steady state > 2 Hz
|
Suppliers with verified business licenses