AVR R250
|
|||||
Voltage regulation
|
Around ± 0.5 %
|
||||
Supply range
|
85 to 139 V
|
||||
Potentiometer for voltage setting
|
1000Ω /0.5W min. setting range ±5%
|
||||
Operating at 50 Hz
|
Threshold at 48 Hz without LAM forimpactsbetween 30 and 40% of the rated
Load
|
||||
Threshold at 48 Hz with LAM 13% forimpacts between 40 and 70% of the rated
Load.
|
|||||
Threshold at 48 Hz with LAM 25% for impacts > 70% of the rated load
|
|||||
Operating at 60 Hz
|
Threshold at 58 Hz without LAM forimpacts between 30 and 40% of the
Rated load
|
||||
Threshold at 58Hz with LAM 13% for impacts 40 and 70% of the rated load
|
|||||
Threshold at 58Hz with LAM 25% for impacts > 70% of the rated load
|
|||||
Specific operating
|
Threshold at 57Hz without LAM for speed variations at a steady state > 2 Hz
|
||||
Threshold at 65Hz without LAM for speed and tractelec / gearlec (U/F gradient)
|
|||||
Special: the factory setting 48Hz 2U/F gradient; a special programme is
Possible on request.
|
|||||
Threshold at 47.5 Hz without LAM for speed variations at a steady state > 2 Hz
|