KEY FEATURES
KEY BENEFITS
Display sets on load on modules LCD display.
On the pages that show the modules MSC link the modules MSC ID and which sets are on load are visible.
Power curve simulation.
Simulation injection testing has been added to the tools menu in the DSE Configuration Suite Software. This feature allows users to demonstrate power curves.
Configurable engine icons.
The DTC related icon screen is user configurable. The user has the option to define the icons and conditions.
Serial port settings within the front panel editor.
RS232 and RS485 settings for Slave ID and Baud Rate have been added to the front panel editor. A new page "Editor - Communications" has been added which contains 4 screens (RS232 Baud, RS232 Slave ID, RS485 Baud, RS485 Slave ID).
Multiple mains (utility) capability (with additional module).
To monitor alternative mains supplies to ensure generator power is supplied at the exact time required.
Mains (Utility) failure detection, mains (utility) power monitoring (kW, kV Ar, kV A & pf) monitoring, mains (utility) decoupling protection, mains (utility) kW export protection.
Gives full mains (utility) back-up and provides no break synchronisation that includes peak lopping and peak shaving options with mains (utility) power monitoring.
Sequential set start.
Allows control over the number of sets starting at any one time. E.g. All start or start on load demand.
Configurable inputs/outputs (12/8).
Provides multiple installation options.
Drag and drop advanced PLC editor.
The PLC editor has been completely redesigned. It has a brand new look and feel and offers enhanced functionality for the user, through the addition of new function blocks. The PLC editor is accessed via DSE configuration suite software. The PLC software
Power monitoring (kW h, kVAr, kv Ah, kV Ar h), reverse power protection, kW overload protection.
Provides clear accurate power measurement information.
Data logging (USB Memory Stick).
Provides current and historical status information.
DSE Configuration Suite PC Software.
Provides complete user-friendly configuration and easy-to-use high-level system control & monitoring.
Tier 4 CAN engine support.
Ensures the control module can be used with the latest in modern electronic engine technology.
DC SUPPLY
CONTINUOUS VOLTAGE RATING
8 V to 35 V continuous
CRANKING DROPOUTS
Able to survive 0 V for 50 mS, providing supply was at least 10 V before dropout and supply recovers to 5 V. This is achieved without the need for internal batteries
MAXIMUM OPERATING CURRENT
460 mA at 12 V, 245 mA at 24 V
MAXIMUM STANDBY CURRENT
375 mA at 12 V, 200 mA at 24 V
CHARGE FAIL/EXCITATION RANGE
0 V to 35 V
OUTPUTS
OUTPUT A (FUEL)
15 A DC at supply voltage
OUTPUT B (START)
15 A DC at supply voltage
OUTPUTS C & D
8 A AC at 250 V AC (Volt free)
AUXILIARY OUTPUTS E,F,G,H,I & J
2 A DC at supply voltage
GENERATOR & BUS
VOLTAGE RANGE
15 V to 333 V AC (L-N)
FREQUENCY RANGE
3.5 Hz to 75 Hz
MAGNETIC PICK-UP
VOLTAGE RANGE
+/- 0.5 V to 70 V
FREQUENCY RANGE
10,000 Hz (max)
MINIMUM LOAD IMPEDANCE
1000Ω
Fully isolated
GAIN VOLTAGE
0 V to 10 V DC
Fully isolated
OFFSET VOLTAGE
+/- 10 V DC
Fully isolated
BUILT-IN AVR CONTROL
MINIMUM LOAD IMPEDANCE
1000Ω
Fully isolated
GAIN VOLTAGE
0 V to 10 V DC
Fully isolated
OFFSET VOLTAGE
+/- 10 V DC
Fully isolated