InteliDrive FPC Engine Controller Designed for Diesel Driven Fire Pump Applications
Product description
Fire Pump Controller is a comprehensive controller for single engine pump sets. The Fire Pump Controller functionality corresponds to NFPA 20 standard.
Controller automatically starts, stops the engine on external signal (see Remote Start/Stop) in AUT mode or by pressing panel push buttons if there are no active
or not confirmed Sd alarms active in TEST mode. Controller ignores engine protections except Emergency Stop and Overspeed protection in AUTO mode.
Key features
Support of engines equipped with Electronic Control Unit (ECU) - J1939
Analog gauge (VDO, Datcon) outputs - operator friendly
Engine speed control
3 configurable analog inputs + 2 analog inputs of battery voltage measurement
7 configurable binary inputs and outputs
6 LED indicators (Alarm, Warning, Not Ready, Running, Battery A, Battery B) Selectable protections alarm/shutdown
1 level of password protection
USB, RS485/RS232/Modem/Modbus communication
Automatic SMS on alarm
On-line control and monitoring over web pages
(embedded web server) via IB-Lite 2 languages (user changeable)
Real time clock and event history log
Push buttons for simple control, lamp test
Front panel sealed to IP65
Based on the NFPA20 standards
Comparator with hysteresis regulation
Technical data
Dimensions 180 × 120 × 55 mm
Weight 450 g
Dimensions and weight
Power supply range 8-36 VDC
Power consumption
0.104 A / 8 V DC
0.080 A / 12 V DC
0.051 A / 24 V DC
0.044 A / 30 V DC
0.040 A / 36 V DC
Allowed supply
voltage drop-out:
100 ms from min. 10 V return to
min. 8 V
Battery voltage
measurement
tolerance
2 % at 24 V
Power supply
temperature
-20 ˚C to +70 ˚C
Storage temperature
-30 ˚C to +80 ˚C
Protection degree
(front panel)
IP65
Impact protection
EN 62262, EN 50102 (IK04)
Humidity
95 % without condensation
Standard conformity
Low Voltage Directive
not applied
Electromagnetic
Compatibility
EN 50081-1:94, EN 50081- 2:96
EN 50082-1:99, EN 50082- 2:97
Vibration
5-25 Hz, ±1.6 mm
25-100 Hz, a = 4 g
Shocks
a = 200 m/s2
Heat radiation
3.5 W
Operating conditions
Number 7
Input resistance 4.2 kΩ
Input range 0 -36 V DC
Close/Open indication
0-2 V DC closed contact